Inverter settings

Dieser Inhalt ist noch nicht in deiner Sprache verfügbar.

Check all inverter settings as described in the Solis inverter user manual. The following settings are specific to modual and must be applied without exception, on every inverter of the system.

Setting Value
Allow Grid Charging Enable
Setting Value
Battery type Lithium Battery HV
Max. charging current 50 A
Max. discharge current 50 A
Forced discharge 4 % or higher
Over-discharge 5 % or higher
Recovery 6 % or higher
Battery Saver Enable
Max. charge SOC 100 % at most

In Switzerland, set the country code NA-EEA-A. Secure the protection parameters against unauthorised changes (see AC side).

Setting Value
Energy meter Eastron, or no energy meter (Solar Manager)
Parallel settings 1 system (Pro 35), or multiple systems (Pro 70) as described in the Solis manual

The password for connecting the Solis Cloud app in local mode depends on the Solis firmware:

Firmware Password
Newer modual
Older battery_storage