Inverter settings
Ce contenu n’est pas encore disponible dans votre langue.
Check all inverter settings as described in the Solis inverter user manual. The following settings are specific to modual and must be applied without exception, on every inverter of the system.
Storage mode
Section titled “Storage mode”| Setting | Value |
|---|---|
| Allow Grid Charging | Enable |
Battery settings
Section titled “Battery settings”| Setting | Value |
|---|---|
| Battery type | Lithium Battery HV |
| Max. charging current | 50 A |
| Max. discharge current | 50 A |
| Forced discharge | 4 % or higher |
| Over-discharge | 5 % or higher |
| Recovery | 6 % or higher |
| Battery Saver | Enable |
| Max. charge SOC | 100 % at most |
Country code
Section titled “Country code”In Switzerland, set the country code NA-EEA-A. Secure the protection parameters against unauthorised changes (see AC side).
Installation-specific settings
Section titled “Installation-specific settings”| Setting | Value |
|---|---|
| Energy meter | Eastron, or no energy meter (Solar Manager) |
| Parallel settings | 1 system (Pro 35), or multiple systems (Pro 70) as described in the Solis manual |
Solis Cloud app, local mode
Section titled “Solis Cloud app, local mode”The password for connecting the Solis Cloud app in local mode depends on the Solis firmware:
| Firmware | Password |
|---|---|
| Newer | modual |
| Older | battery_storage |