Check all inverter settings as described in the Solis inverter user manual. The following
settings are specific to modual and must be applied without exception, on every inverter
of the system.
| Setting |
Value |
| Allow Grid Charging |
Enable |
| Setting |
Value |
| Battery type |
Lithium Battery HV |
| Max. charging current |
50 A |
| Max. discharge current |
50 A |
| Forced discharge |
4 % or higher |
| Over-discharge |
5 % or higher |
| Recovery |
6 % or higher |
| Battery Saver |
Enable |
| Max. charge SOC |
100 % at most |
In Switzerland, set the country code NA-EEA-A. Secure the protection parameters against
unauthorised changes (see AC side).
| Setting |
Value |
| Energy meter |
Eastron, or no energy meter (Solar Manager) |
| Parallel settings |
1 system (Pro 35), or multiple systems (Pro 70) as described in the Solis manual |
The password for connecting the Solis Cloud app in local mode depends on the Solis firmware:
| Firmware |
Password |
| Newer |
modual |
| Older |
battery_storage |